Unigy II Spacesaver Installation Manual
Fig. 3-1A
Fig. 3-2
JOINING PLATE
TOP MODULE ONLY
TOP MODULE SLIDES INTO CUT
OUTS OF BOTTOM MODULE
(NO BOLTING NEEDED)
TORQUE TO 50 in. lbs.
(5.6 Nm)
LIFT STRAP
LOCK WASHER
3/8-16 X 1 1/4" BOLT
MOUNTING SUPPORT
Interlock™ System Leveling
When leveling Unigy II Interlock™ battery systems that are
installed with a 1-piece base support, it is critical to note that
the back channel is 3/16" shorter than the front channel.
If a level is placed across the front and rear channels, a 3/16" shim
should be placed on top of the rear channel in order to level properly.
9