Installation Guide
Table Of Contents
- Dell EMC PowerSwitch N3200-ON Series Installation Guide
- About this guide
- N3200-ON Series switch
- Site preparations
- N3200-ON Series switch installation
- Unpack
- Rack or cabinet hardware installation
- Ground cable
- Desktop
- N3208PX-ON ceiling-mount switch installation
- N3208PX-ON wall-mount switch installation
- Standard bracket two-post installation
- Two-post five-inch-offset switch installation
- Two-post flush-mount switch installation
- Wall- or ceiling-mount switch installation
- One RU ReadyRails installation
- Optics installation
- Switch start-up
- After switch placement
- Switch replacement
- External power adapter
- Power adapter holder assembly
- Wall or ceiling installation
- DIN rail installation
- Single-EPA and switch four-post installation
- Single-EPA and switch two-post center-mount installation
- Single-EPA and switch two-post front-mount installation
- Dual-EPAs two-post front-mount installation
- Dual-EPAs two-post center-mount installation
- Power supply
- Fans
- Management ports
- Installation using ONIE
- Specifications
- Dell EMC support
Power supply
The N3200-ON Series switch ships with one pluggable AC power supply. You can order a second AC PSU separately. If you
require DC power, you can order one or two DC PSUs.
The N3224PX-ON, N3248P-ON, and N3248PXE-ON switches also support an optional external power supply that connects to
the switch using an MPS-1S or MPS-3S shelf. Use the EPS to add redundancy, or extend the PoE budget based on your
requirement. To install an external power supply, see the External Power Supply (EPS) Installation for the Dell EMC
PowerSwitch N2200-ON and N3200-ON Series Switches at www.dell.com/support.
Table 10. AC PSU input voltage
AC PSU Input voltage Output
DPS-320AP (For N3208PX-ON only)
● Low line = 110 V
● High line = 220 V
● 300 W
● 300 W
DPS-550
● Low line = 110 V
● High line = 220 V
● 550 W
● 550 W
DPS-1050
● Low line = 110 V
● High line = 220 V
● 950 W
● 1050 W
DPS-1600
● Low line = 110 V
● High line = 220 V
● 950 W
● 1600 W
Table 11. DC PSU input voltage
DC PSU Input voltage Output
DPS-550
● -40 V to -60 V ● 550 W
DPS-1300
● -40 V to -60 V ● 1300 W
CAUTION: To prevent electrical shock, ensure that the N3200-ON Series switch is grounded properly. If you do
not ground your equipment correctly, excessive emissions may result. Use a qualified electrician to ensure that
the power cables meet your local electrical requirements.
WARNING: Equipment that provides DC input to the DC port must be certified for CCC and meet the relevant
standards.
NOTE: Reserve airflow, from the PSU-side to the I/O-side of the switch, is only supported on the N3224T-ON, N3248X-
ON, and N3248TE-ON switches.
NOTE: Connect the power supply to the appropriate branch circuit protection as defined by your local electrical codes.
Verify that the remote power source complies with the switch input power specifications.
NOTE: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap
when handling the N3200-ON Series switch and components.
Topics:
• Components
• AC or DC power supply installation
• AC or DC power supply replacement
• 550W DC power connections
• 1300W DC power connections