Messages Reference Guide

550 Fabric OS Message Reference
53-1002749-01
HIL-1107
5
HIL-1107
Message Switch faulted, <nominal voltage> (<measured voltage>) above threshold. System
preparing for reset.
Message Type FFDC | LOG
Severity CRITICAL
Probable Cause Indicates that the switch voltage is above threshold. This message is specific to non-bladed switches.
Recommended
Action
For switches that do not have field-replaceable units (FRUs), replace the entire switch.
If the 12 volt level is faulty, replace one or both power supplies; if any other voltage is faulty, replace the
entire switch.
HIL-1108
Message Switch faulted, <nominal voltage> (<measured voltage>) below threshold. System
preparing for reset.
Message Type FFDC | LOG
Severity CRITICAL
Probable Cause Indicates that the switch voltage is below threshold. This message is specific to non-bladed switches.
Recommended
Action
For switches that do not have field-replaceable units (FRUs), replace the entire switch.
If the 12 volt level is faulty, replace one or both power supplies; if any other voltage is faulty, replace the
entire switch.
HIL-1201
Message Blower <blower number>, speed (<measured speed> RPM) above threshold.
Message Type LOG
Severity WARNING
Probable Cause Indicates that the fan speed (in RPM) has risen above the maximum threshold. A high speed does not
necessarily mean that the fan is faulty.
Recommended
Action
Run the tempShow command to verify that the switch temperatures are within operational ranges. Refer
to the hardware reference manual for the temperature range of your switch.
Make sure that the area is well-ventilated and that the room temperature is within the operational range
of your switch. Refer to the hardware reference manual for your switch for the operational temperature
range.
Run the fanShow command to monitor the speed of the fan generating this error.
If the fan continues to generate this message, replace the fan FRU.