Setup Guide

464 Brocade Fabric OS Message Reference
53-1004119-01
HIL-1514
5
HIL-1514
Message Blade in slot <slot number> is shutting down.
Message Type FFDC | LOG
Severity CRITICAL
Probable Cause Indicates that the temperature of this blade has been above the maximum threshold for at least two
minutes. The blade is shut down to prevent damage. This usually follows a high-temperature warning
message.
Recommended
Action
Run the fanShow command to verify all the fans are working properly.
Make sure that the area is well-ventilated and that the room temperature is within the operational range
of your switch. Refer to the hardware reference manual for your switch for the operational temperature
range.
If the message persists, replace the faulty blade.
HIL-1515
Message High temperature (<measured temperature> C) exceeds system temperature limit.
System will shut down soon.
Message Type FFDC | LOG
Severity CRITICAL
Probable Cause Indicates that temperatures in the system have risen above the critical threshold.
Recommended
Action
Run the fanShow command to verify that all fans are working properly. Replace any deteriorating fan
field-replaceable units (FRUs).
Make sure that the area is well-ventilated and that the room temperature is within the operational range
of your switch. Refer to the hardware reference manual for your switch for the operational temperature
range.
HIL-1601
Message Using backup temperature sensor. Attention needed.
Message Type LOG
Severity ERROR
Probable Cause Indicates that temperature readings from the primary sensor are out of range.
Recommended
Action
Run the fanShow command to verify that all fans are operating correctly. Replace any deteriorating fan
field-replaceable units (FRUs).
Run the tempShow command to verify temperature values. If any sensor is too high, monitor the switch.
Try rebooting or power cycling the switch.