Owner's Manual

CMC Property Database Group and Object Definitions 351
# cfgChassisRedundancyReserve
Read only. Indicates the amount of redundant power (in watts) in reserve
that can be utilized in the event of an AC grid or PSU failure. This value is 0
if the Redundancy Policy is set to 0 (no redundancy).
# cfgChassisLoadSharing
Read only. Indicates the amount of power that is lost due to load sharing
between multiple PSUs. The load sharing value varies between 54–423 watts,
depending on the number of PSUs in the system.
# cfgChassisBaseConsumption
Read only. Indicates the estimated cumulative DC output power
consumption (in watts), determined from a field replaceable unit (FRU) on
the hardware modules in the chassis.
# cfgChassisServerAllocation
Read only. Indicates (in watts) the cumulative power allocated to servers.
# cfgChassisOverallPowerConsumption
Read only. Indicates the cumulative AC input power consumption data (in
watts) captured from all healthy and functional PSUs in the chassis.
cfgChassisPowerWarningThreshold
Indicates the maximum amount of power (in watts) beyond which the CMC
takes action to reduce power consumption.
Default: 7928
If cfgChassisDynamicPSUEngagementSet is set to 1 (enabled) and the
chassis power consumption exceeds the power warning threshold, then the
performance of lower priority servers is reduced until total power
consumption falls below the threshold.
If cfgChassisDynamicPSUEngagementSet is set to 0 (disabled), servers with
lower priority may be powered off until total power consumption falls below
the threshold.