248 Using the iKVM Module
The message "User has been disabled as
another appliance is currently tiered"
appears on the monitor connected to the
rear panel.
A network cable is connected to the iKVM
ACI port connector and to a secondary
KVM appliance.
Only one connection is allowed at a time.
The ACI tiering connection has
precedence over the rear panel monitor
connection. The precedence order is front
panel, ACI, and then rear panel.
The iKVM’s amber LED is blinking. There are three possible causes:
There is problem with the iKVM, for
which the iKVM requires reprogramming.
To fix the problem, follow the
instructions for updating iKVM firmware
(see "Updating the iKVM Firmware" on
page 245).
The iKVM is reprogramming the CMC
Console Interface. In this case, the CMC
Console is temporarily unavailable and
represented by a yellow dot in the OSCAR
interface. This process takes up to
15 minutes.
The iKVM firmware has detected a
hardware error. For additional
information, view the iKVM status.
To view iKVM status using the Web
interface:
1
Log in to the CMC Web interface.
2
Select iKVM in the system tree, and
then click
Properties
.
To view iKVM status using RACADM,
open a Telnet/SSH text console to the
CMC, log in, and type:
racadm getkvminfo
Table 9-6. Troubleshooting iKVM (continued)
Problem Likely Cause and Solution