User's Manual

Power Management 221
Power Budgeting for Hardware Modules
The figure below illustrates a chassis that contains a six-PSU configuration.
The PSUs are numbers 1 - 6, starting on the left-side of the enclosure.
Figure 8-1. Chassis With Six-PSU Configuration
The CMC maintains a power budget for the enclosure that reserves the
necessary wattage for all installed servers and components. When a server is
powered-up in an enclosure, the iDRAC software reports the following to the
CMC:
The maximum power the server is capable of consuming based on its
memory and CPU configuration.
The minimum power the server should be allocated to ensure proper
operation.
The CMC will grant the server its maximum power, if available, or a value
between the maximum and minimum if not, and the allocated wattage is
subtracted from the available budget. Once the server is granted a power
request, the server's iDRAC software will monitor the actual power
PSU1 PSU2 PSU3 PSU4 PSU5 PSU6