User's Manual

244 Power Management
Table 8-13. Server Modules
Item Description
Slot Displays the location of the server module. The Slot is a sequential
number (1–16) that identifies the server module by its location
within the chassis.
Name Displays the server name. The server name can be redefined by the
user.
Ty p e Displays the type of the server.
Priority Indicates the priority level allotted to the server slot in the chassis
for power budgeting. The CMC uses this value in its calculations
when power must be reduced or reallocated based on user-defined
power limits or power supply or power grid failures.
Priority levels: 1 (highest) through 9 (lowest)
Default: 1
NOTE: Server slot priority level is associated with the server
slot—not with the server inserted into the slot. If you move a server to
a different slot in the chassis or to a different chassis, the priority
previously associated with new slot determines the priority of the
relocated server.
Power State Displays the power status of the server:
N/A:
The CMC has not determined the power state of the
server.
Off:
Either the server or chassis is off.
On:
Both chassis and server are on.
Powering On
: Temporary state between Off and On. When the
powering on cycle completes, the Power State will change to On.
Powering Off:
Temporary state between On and Off. When the
powering off cycle completes, the Power State will change to Off.
Budget
Allocation -
Minimum,
Actual
Displays the power budget allocation for the server module.
Minimum:
Minimum budget allocation possible for each server.
Actual:
Current power budget allocation for each server.