Table 78. Particulate contamination specifications
Particulate contamination Specifications
Air filtration
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE: This condition applies to data center environments
only. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE: Air entering the data center must have MERV11 or
MERV13 filtration.
NOTE: Air filtering can also be accomplished by filtering
room air with MERV8 filter per ANSI/ASHARE Standard
127.
Conductive dust Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE: This condition applies to data center and non-data
center environments.
NOTE: Common sources of conductive dust include
manufacturing processes, and zinc whiskers from the
plating on the bottom of raised floor tiles.
Corrosive dust Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
NOTE: This condition applies to data center and non-data
center environments.
Table 79. Gaseous contamination specifications
Gaseous contamination Specifications
Copper Coupon Corrosion rate <300 Å/month per Class G1 as defined by ANSI/
ISA71.04-2013
Silver Coupon Corrosion rate <200 Å/month as defined by ANSI/ISA71.04-2013
NOTE: Maximum corrosive contaminant levels measured at 50% relative humidity.
Thermal restriction matrix
Table 80. Thermal restriction matrix for processor and fans
Configuration 8 x 2.5-inch
Processor TDP Processor cTDP Max
120 W 150 W STD fan
STD heat sink
155 W 180 W STD fan
STD heat sink
180 W 200 W STD fan
HPR heat sink
Technical specifications 137