Table 23. Maximum vibration specications
Maximum vibration Specications
Operating 0.26 G
rms
at 5 Hz to 350 Hz (all operation orientations).
Storage 1.88 G
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
Table 24. Maximum shock specications
Maximum shock Specications
Operating Six consecutively executed shock pulses in the positive and negative x, y,
and z axes of 6 G for up to 11 ms.
Storage Six consecutively executed shock pulses in the positive and negative x, y,
and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Table 25. Maximum altitude specications
Maximum altitude Specications
Operating
3048 m (10,000 ft)
Storage 12,000 m (39,370 ft)
Table 26. Operating temperature de-rating specications
Operating temperature de-rating Specications
Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m
(3,117 ft).
35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m
(3,117 ft).
40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m
(3,117 ft).
Standard operating temperature
Table 27. Standard operating temperature
specications
Standard operating temperature Specications
Continuous operation (for altitude less than 950 m or 3117
ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.