PS Series 3000 QuickStart Step 1. Set Up the Array Hardware
6
B. Mount Array in a Stable Rack
A PS Series array must be mounted in a two-pole or four-pole 19” rack.
Instructions for rack assembly and mounting an array are included with the
two-pole assembly kit and the four-pole assembly kit in the array shipping box.
When mounting an array in a rack, you must meet the following recommendations
and requirements:
Be sure there is sufficient space for air flow in front of and behind the array.
It is recommended that you attach the rack to the floor for added stability.
Be sure to support the array until it is completely mounted in the rack.
The location of the array must be properly vented and must meet the
environmental, power, and physical requirements described in the
following table.
PS Series Storage Array Requirements
Component Requirement
Weight of fully-loaded array 80 pounds or 36.36 kilograms
Operating temperature 41 to 104 degrees F / 5 to 40 degrees C
Storage temperature -22 to 140 degrees F / -30 to 60 degrees C
Maximum altitude 10,000 feet
Operational relative humidity 8 to 90% non-condensing
Thermal output of fully-loaded array 2200 BTU/hour, 660 watts
Shock 30 G for 2 ms
Vibration .1 G @ 10 to 100 hertz
Input voltage 90 to 264 VAC (auto-sensing)
Input current 5.5 amperes (maximum, single power supply)
@ 120 volts
Input frequency 50 to 60 hertz
Input power 660 VA
Power supplies Dual, 450 watts DC output
Height/Width/Depth 5.25” x 17 5/8” x 22.5”
13.33 cm x 44.77 cm x 56.25 cm