Technical Guide
Table Of Contents
- Dell EMC PowerEdge R350 Technical Guide
- Contents
- System overview
- System features and generational comparison
- Chassis views and features
- Processor
- Memory subsystem
- Storage
- Networking
- Expansion cards and expansion card risers
- Power, thermal, and acoustics
- Rack, rails, and cable management
- Supported operating systems
- Dell EMC OpenManage systems management
- Dell Technologies Services
- Dell EMC ProDeploy Enterprise Suite
- Dell EMC Data Migration Service
- Dell EMC ProSupport Enterprise Suite
- Dell EMC ProSupport Plus for Enterprise
- Dell EMC ProSupport for Enterprise
- Dell EMC ProSupport One for Data Center
- ProSupport for HPC
- Support Technologies
- Services for Data Security
- Dell Technologies Education Services
- Dell Technologies Consulting Services
- Dell EMC Managed Services
- Appendix A. Additional specifications
- Appendix B. Standards compliance
- Appendix C Additional resources
Table 30. Continuous Operation Specifications for ASHRAE A3
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
5–40°C (41–104°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 85% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/175 m (33.8°F/574 Ft) above
900 m (2953 Ft)
Table 31. Continuous Operation Specifications for ASHRAE A4
Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
5–45°C (41–113°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/125 m (33.8°F/410 Ft) above
900 m (2953 Ft)
Table 32. Common Environmental Specifications for ASHRAE A2, A3, A4
Allowable continuous operations
Maximum temperature gradient (applies to both
operation and non-operation)
20°C in an hour* (36°F in an hour) and 5°C in 15 minutes (41°F in 15
minutes), 5°C in an hour* (41°F in an hour) for tape
NOTE: * - Per ASHRAE thermal guidelines for tape hardware, these are
not instantaneous rates of temperature change.
Non-operational temperature limits -40 to 65°C (-104 to 149°F)
Non-operational humidity limits 5% to 95% RH with 27°C (80.6°F) maximum dew point
Maximum non-operational altitude 12,000 meters (39,370 feet)
Maximum operational altitude 3,048 meters (10,000 feet)
Table 33. Maximum vibration specifications
Maximum vibration Specifications
Operating 0.26 G
rms
at 5 Hz to 350 Hz (all operation orientations)
Storage 1.88 G
rms
at 10 Hz to 500 Hz for 15 minutes (all six sides tested)
Table 34. Maximum shock pulse specifications
Maximum shock pulse Specifications
Operating Six consecutively executed shock pulses in the positive and negative x, y,
and z axis of 6 G for up to 11 ms.
Storage Six consecutively executed shock pulses in the positive and negative x, y,
and z axis (one pulse on each side of the system) of 71 G for up to 2 ms.
Thermal restrictions
ASHRAE A3/A4 Thermal restriction
The following list is the restriction for supporting fresh air in all the platform:
Appendix A. Additional specifications
51