Table 19. Particulate contamination specifications (continued)
Particulate contamination Specifications
NOTE: This condition applies to data center and non-data
center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
NOTE: This condition applies to data center and non-data
center environments.
Table 20. Gaseous contamination specifications
Gaseous contamination Specifications
Copper Coupon Corrosion rate <300 Å/month per Class G1 as defined by ANSI/
ISA71.04-2013
Silver Coupon Corrosion rate <200 Å/month as defined by ANSI/ISA71.04-2013
NOTE: Maximum corrosive contaminant levels measured at 50% relative humidity.
Thermal air restrictions
Two PSUs are required in redundant mode, however PSU failure is not supported.
Non Dell qualified peripheral cards or peripheral cards greater than 25 W are not supported.
GPU is not supported.
The operating temperature is for a maximum altitude of 950 m for fresh air cooling.
Because of single fan in the system, cooling redundancy is not supported.
NOTE: DIMM blank is not required.