Line-Interactive Rack UPS User's Guide

66
|
Specifications
Table 12. Electrical Input
100/120V Models 208V Models 230V Models
Nominal Voltage 100/120V 208V 230V
Voltage Range 84–150V auto-sensing 160–278V auto-sensing 160–286V auto-sensing
Nominal Frequency 50/60 Hz auto-sensing, ±3 Hz
Efficiency (Normal mode) >95%
Noise Filtering Full-time EMI/RFI filtering
Connections 1000W: IEC 320-C14
input connector, 15A
1920/1500W: IEC
320-C20 input connector,
20A
2700/2300W: 2m, L5-30P
attached power cord
2700W: IEC 320-C20
input connector, 16A
1000W: IEC 320-C14
input connector, 10A
1920W: IEC 320-C14
input connector, 10A
2700W: IEC 320-C20
input connector, 16A
Table 13. Electrical Output
100/120V Models 208V Models 230V Models
Power Levels
(rated at nominal inputs)
1000W
1920/1500W
2700/2300W
2700W 1000W
1920W
2700W
Regulation (Normal mode) 100V: 92–108V
110V: 100–121V
120V: 106–132V
200V: 180–220V
208V: 184–228V
220V: 198–243
230V: 208–253V
240V: 216–264V
Regulation (Battery mode),
Nominal Voltage ±5%
Same as line mode
Voltage Waveform Sine wave
Output Receptacles 1000W: (4) 5-15R, 15A;
(2) IEC 320-C13, 15/10A
1920/1500W:
(6) 5-15/5-20R, 20A;
(2) IEC 320-C19, 20/16A;
(2) IEC 320-C13, 15/10A
2700/2300W: (1) L5-20R,
20A; (2) 5-15/5-20R, 20A;
(2) IEC 320-C19, 20/16A;
(2) IEC 320-C13, 15/10A
2700W: (2) L6-30R, 20A;
(2) IEC 320-C19, 20A;
(2) IEC 320-C13, 15/10A
1000W: (4) IEC 320-C13,
15/10A; (2) IEC 320-C13,
15/10A
1920W: (2) IEC 320-C19,
20/16A; (6) IEC 320-C13,
15/10A; (2) IEC 320-C13,
15/10A
2700W: (2) IEC 320-C19,
20/16A; (6) IEC 320-C13,
15/10A; (2) IEC 320-C13,
15/10A