Users Guide

Provides the statistics for CPU, memory, IO utilization, and the system level CUPS index. If the host system is powered off, then
the graph displays the power off line below 0 percent.
You can reset the peak utilization for a particular sensor. Click Reset Historical Peak. You must have Configure privilege to reset
the peak value.
Performance Metrics section:
Displays status and present reading
Displays or specifies the warning threshold utilization limit. You must have server configure privilege to set the threshold values.
For information about the displayed properties, see the iDRAC Online Help.
Monitoring performance index for of CPU, memory, and
input output modules using RACADM
Use the SystemPerfStatistics sub command to monitor performance index for CPU, memory, and I/O modules. For more information,
see the iDRAC RACADM CLI Guide available at www.dell.com/idracmanuals.
Checking the system for Fresh Air compliance
Fresh Air cooling directly uses outside air to cool systems in the data center. Fresh Air compliant systems can operate above its normal
ambient operating range (temperatures up to 113 °F (45 °C)).
NOTE: Some servers or certain configurations of a server may not be Fresh Air compliant. See the specific server
manual for details related to Fresh Air compliance or contact Dell for more details.
To check the system for Fresh Air compliance:
1. In the iDRAC Web interface, go to System > Overview > Cooling > Temperature overview.
The Temperature overview page is displayed.
2. See the Fresh Air section that indicates whether the server is fresh air compliant or not.
Viewing historical temperature data
You can monitor the percentage of time the system has operated at ambient temperature that is greater than the normally supported
fresh air temperature threshold. The system board temperature sensor reading is collected over a period of time to monitor the
temperature. The data collection starts when the system is first powered on after it is shipped from the factory. The data is collected and
displayed for the duration when the system is powered on. You can track and store the monitored temperature for the last seven years.
NOTE:
You can track the temperature history even for systems that are not Fresh-Air compliant. However, the
threshold limits and fresh air related warnings generated are based on fresh air supported limits. The limits are 42ºC for
warning and 47ºC for critical. These values correspond to 40ºC and 45ºC fresh air limits with 2ºC margin for accuracy.
Two fixed temperature bands are tracked that are associated to fresh air limits:
Warning band — Consists of the duration a system has operated above the temperature sensor warning threshold (42ºC). The
system can operate in the warning band for 10% of the time for 12 months.
Critical band — Consists of the duration a system has operated above the temperature sensor critical threshold (47ºC). The system
can operate in the critical band for 1% of the time for 12 months which also increments time in the warning band.
The collected data is represented in a graphical format to track the 10% and 1% levels. The logged temperature data can be cleared only
before shipping from the factory.
An event is generated if the system continues to operate above the normally supported temperature threshold for a specified operational
time. If the average temperature over the specified operational time is greater than or equal to the warning level (> = 8%) or the critical
level (> = 0.8%), an event is logged in the Lifecycle Log and the corresponding SNMP trap is generated. The events are:
Warning event when the temperature was greater than the warning threshold for duration of 8% or more in the last 12 months.
Critical event when the temperature was greater than the warning threshold for duration of 10% or more in the last 12 months.
Warning event when the temperature was greater than the critical threshold for duration of 0.8% or more in the last 12 months.
Critical event when the temperature was greater than the critical threshold for duration of 1% or more in the last 12 months.
You can also configure iDRAC to generate additional events. For more information, see the Setting alert recurrence event section.
Viewing iDRAC and managed system information
103