User`s guide

62
|
Serial Interface Operation
sensors command
Use this command to retrieve values or set temperature and humidity thresholds for environment monitoring
sensors connected to an rPDU.
Usage
rPDU>sensors[name]
rPDU>sensors threshold [[name] [<thresholds>]
where:
[name] = Valid identifier for temperature sensor (T1) or humidity sensor (H1)
<thresholds> = High or low threshold values, entered in whole numbers, separated by a space
Retrieve present sensor readings for each environment monitoring sensor connected to an rPDU
rPDU>sensors
Example
rPDU>sensors
rPDU: temperature on sensor T1: 33.3C.
rPDU: humidity on sensor H1: 50%.
rPDU: dry-contact sensor D1 is opened.
rPDU: dry-contact sensor D2 is opened.
Retrieve present thresholds for all environment monitoring sensors connected to an rPDU
rPDU>sensors threshold
Example
rPDU>sensors threshold
rPDU: temperature thresholds on sensor T1: 60.0C:59.0C.
rPDU: humidity thresholds on sensor H1: 10.0%:0.0%.
NOTE:
The retrieved threshold value displays in a format of high value, then low value, separated by colons.
Retrieve present thresholds for a specific environment monitoring sensor connected to an rPDU
rPDU>sensors threshold [name]
Example
rPDU>sensors threshold T1
rPDU: temperature thresholds on sensor T1: 60.0C:59.0C.
NOTE:
The retrieved threshold value displays in a format of high value, then low value, separated by colons..
Set thresholds for a specific environment monitoring sensor connected to an rPDU
rPDU>sensors threshold[name] [<thresholds>]
NOTE:
The threshold values are entered in a format of high value, then low value, separated by a space.
Examples
rPDU>sensors threshold T1 55 50
rPDU: temperature thresholds on sensor T1: 55.0C:50.0C.
rPDU>sensors threshold H1 15 5
rPDU: humidity thresholds on sensor H1: 15.0%:5.0%.