User`s guide

65
Serial Interface Operation
|
Retrieve the input voltage for a specific phase line (Three-phase rPDUs only)
rPDU>[XN|YN|ZN|XZ|XY|YZ]
Three-Phase Wye Example
rPDU>voltage XN
rPDU: RMS voltage between X and N: 230V.
Three-Phase Delta Example
rPDU>voltage XY
rPDU: RMS voltage between X and Y: 208V.
Retrieve a summary of the input voltage for rPDU phase lines (Three-phase rPDUs only)
rPDU>voltage [summary]
NOTE:
The summary option retrieves the voltage summary for each phase.
NOTE: The summary option response displays the present power as the first parameter and the peak consumption watts
as the second parameter. The minimum and average values will always be reported as zero.
Three-Phase Wye Example
rPDU>voltage summary
XN:229V,0V,0V,0V
YN:230V,0V,0V,0V
ZN:231V0V,0V,0V
Three-Phase Delta Example
rPDU>voltage summary
XY:208V, 0V,0V,0V.
YZ:209V, 0V,0V,0V.
XZ:207V, 0V,0V,0V.
Retrieve a summary of the input voltage for a specific phase line (Three-phase rPDUs only)
rPDU>voltage [summary] [XN|YN|ZN|XZ|XY|YZ]
Three-Phase Wye Example
rPDU>voltage summary XN
XN:229V,0V,0V,0V.
Three-Phase Delta Example
rPDU>voltage summary YZ
YZ:209V,0V,0V,0V.