110 Storage Management Message Reference
2335 Controller event
log: %1
Warning /
Non-critical
Cause: The %1 indicates a substitution
variable. The text for this substitution
variable is generated by the controller and is
displayed with the alert in the Alert Log. This
text is from events in the controller event log
that were generated while Storage
Management was not running. This text can
vary depending on the situation.
Action: If there is a problem, review the
controller event log and the Server
Administrator Alert Log for significant events
or alerts that may assist in diagnosing the
problem. Check the health of the storage
components. See the hardware
documentation for more information.
None 753
2336 Controller event
log: %1
Critical /
Failure /
Error
Cause: The %1 indicates a substitution
variable. The text for this substitution
variable is generated by the controller and is
displayed with the alert in the Alert Log. This
text is from events in the controller event log
that were generated while Storage
Management was not running. This text can
vary depending on the situation.
Action: See the hardware documentation for
more information.
None 754
2337 The controller is
unable to recover
cached data from the
battery backup unit
(BBU).
Critical /
Failure /
Error
Cause: The controller was unable to recover
data from the cache.
Action: Check if the battery is charged and in
good health. When the battery charge is
unacceptably low, it cannot maintain cached
data. Check if the battery has reached its
recharge limit. The battery may need to be
recharged or replaced.
None 1154
2338 The controller has
recovered cached
data from the BBU.
Ok / Normal Cause: This alert is for informational purposes.
Action: None
None 1151
2339 The factory default
settings have been
restored.
Ok / Normal Cause: This alert is for informational purposes.
Action: None
None 751
Table 4-4. Storage Management Messages (continued)
Event
ID
Description Severity Cause and Action Clear
Event
Number
SNMP
Trap