Installation Manual

202 BigIron RX Installation Guide
53-1001811-01
Hardware specifications
8
Table 34 lists the maximum power consumption, in watts, for BigIron RX Series modules.
TABLE 32 Maximum power calculations @ 200 VAC
BigIron RX Series
chassis
Current Amps Watts BTU per hour
BigIron RX-4 6 1217 4155
BigIron RX-8 12 2417 8249
BigIron RX-16 25 4905 16741
BigIron RX-32 57 11353 38746
TABLE 33 Maximum power calculations at 48 VDC
BigIron RX Series
chassis
Amps Watts BTUs per hour
BigIron RX-4 25 1217 4155
BigIron RX-8 50 2417 8249
BigIron RX-16 102 4905 16741
BigIron RX-32 N/A N/A N/A
TABLE 34 Wattage consumed by individual components
Component Maximum power consumption, in Watts
Management modules
Management (BigIron RX-4, -8, and
-16)
30W
Management (BigIron RX-32) 35W
Switch fabric
RX-BI-SFM1 (BigIron RX-4, -8, and -16) 19W
RX-BI-SFM3 (BigIron RX-4, -8, and -16) 53W
RX-BI-32-SFM (BigIron RX-32) 200W
Interface modules
4-port 10 Gigabit Ethernet interface
with fiber-optic modules installed
191W
2-port 10 Gigabit Ethernet interface
with fiber-optic modules installed
110W
24-port Gigabit Ethernet Fiber
Interface with fiber-optic modules
installed
101W
24-port Gigabit Ethernet Copper
Interface
102W
48-port Gigabit Ethernet Copper
Interface
210W
16-port 10 Gigabit Ethernet Interface 245W