C6220 Fresh Air Support
Expanded Operating Temperature
10% of annual
operating hours
5 °C to 40 °C, 5% to 85% RH with 26 °C max. dew point.
For temperatures between 35 °C and 40 °C, de-rate
maximum allowable dry bulb temperature by 1 °C/175
meters above 950 meters (1 °F per 319 feet).
1% of annual
operating hours
5 °C to 45 °C, 5% to 90% RH with 26 °C dew point.
For temperatures between 40 °C and 45 °C, de-rate
maximum allowable dry bulb temperature by 1 °C/125
meters above 950 meters (1 °F per 228 feet).
NOTE: When operating in the expanded temperature
range, ambient temperature warnings may be reported in
the System Event Log.
NOTE: No cold start up below 5 °C.
NOTE: The operating temperature specification is for a
maximum altitude of 3048 meters (10,000 feet).
NOTE: 1U and 2U nodes support the 130W (8 core),
130W (4 core) and 135W processors with the specific
configurations of HDD, PCI-E and Mezzanine card. Refer
to the following statements and matrixes of Fresh Air
Support for details.
The numbers of HDD in the tables below list
the total quantity supported per chassis.
No GPU support.
1U node can’t support PCI-E and Mezzanine
card at the same time.