Owners Manual

Table 14. Expanded operating temperature (continued)
Expanded operating temperature Specifications
5°C-45°C for a maximum of 1% of its annual operating
hours.
For temperatures between 40°C-45°C, derate maximum
allowable temperature by 1°C per 125 m above 950 m (1°F
per 228 ft).
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported in the System
Event Log.
Operating temperature derating specifications
Table 15. Operating temperature
Operating temperature derating Specifications
< 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft)
above 950 meters (3,117 ft)
35°C40°C (95°F104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft)
above 950 meters (3,117 ft)
> 45°C (113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft)
above 950 meters (3,117 ft)
Relative humidity specifications
Table 16. Relative humidity specifications
Relative humidity Specifications
Storage 5% to 95% RH with 33°C (91°F) maximum dew point.
Atmosphere must be non-condensing at all times.
Operating 10% to 80% relative humidity with 29°C (84.2°F) maximum
dew point
Temperature specifications
Table 17. Temperature specifications
Temperature Specifications
Storage 40°C65°C (40°F-149°F)
Continuous operation (for altitude less than 950 m or 3117 ft) 10°C35°C (50°F-95°F) with no direct sunlight on the
equipment.
Fresh air For information about fresh air, see Expanded Operating
Temperature section.
Maximum temperature gradient (operating and storage) 20°C/h (68°F/h)
16 Technical specifications