Reference Guide
Table 19. Gaseous contamination specifications
Gaseous contamination Specifications
Copper coupon corrosion rate <300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
Silver coupon corrosion rate <200 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Maximum vibration specifications
Table 20. Maximum vibration specifications
Maximum vibration Specifications
Operating 0.26 Grms at 5 Hz to 350 Hz (all operation orientations).
Storage 1.88 Grms at 10 Hz to 500 Hz for 15 min (all six sides tested).
Maximum shock specifications
Table 21. Maximum shock specifications
Maximum shock Specifications
Operating 24 executed shock pulses 6 G in the positive and negative x, y, z
axis for up to 11 ms (four pulses on each side of the system).
Storage Six consecutively executed shock pulses of 71 G in the positive and
negative x, y, z axes for up to 2 ms (one pulse on each side of the
system).
Maximum altitude specifications
Table 22. Maximum altitude specifications
Maximum altitude Specifications
Operating 3048 m (10,000 ft)
Storage 12,000 m (39,370 ft)
Fresh Air Operation
Fresh Air operation restrictions
• Processors with a TDP greater than 105 W are not supported
• Support for processors of 85 W and below without PERC restrictions
• 3.5-inch drive configuration is not supported
• 114-mm heat sink is required for the processor in CPU1 socket
• Kerby-flat OCP is not supported
• M.2 card on DCS Mezzanine slot is not supported.
• NVMe SSD is not supported
• AEP DIMM and LRDIMM are not supported
• PCIe cards greater than 25 W are not supported
• H730 PERC and H330 support for 105-W processors
18