Input requirements
Supply voltage: (4860) V DC
Current consumption: 32 A (maximum)
Kit contents
Dell part number 6RYJ9 terminal block or equivalent (1)
#6-32 nut equipped with lock washer (1)
Required tools
Wire-stripper pliers capable of removing insulation from size 10 AWG solid or stranded, insulated copper wire.
NOTE: Use alpha wire part number 3080 or equivalent (65/30 stranding).
Required wires
One UL 10 AWG, 2 m maximum (stranded) black wire [(4860) V DC].
One UL 10 AWG, 2 m maximum (stranded) red wire (V DC return).
One UL 10 AWG, 2 m maximum, green with a yellow stripe, stranded wire (safety ground).
Assembling and connecting safety ground wire
Prerequisites
NOTE:
For equipment using (4860) V DC power supply units (PSUs), a qualified electrician must perform all connections
to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All electrical
wiring must comply with applicable local or national codes and practices. Damage due to servicing that is not authorized by
Dell is not covered by your warranty. Read and follow all safety instructions that came with the product.
Steps
1. Strip the insulation from the end of the green or yellow wire, exposing approximately 4.5 mm (0.175 inches) of copper wire.
2. Using a hand-crimping tool (Tyco Electronics, 58433-3 or equivalent), crimp the ring-tongue terminal (Jeeson Terminals Inc.,
R5-4SA or equivalent) to the green and yellow wire (safety ground wire).
3. Connect the safety ground wire to the grounding post on the back of the system by using a number 6-32 nut that is
equipped with a locking washer.
Figure 160. Assembling and connecting the safety ground wire
1.
#6-32 nut 2. spring washer
3. grounding post 4. safety ground wire
160 Installing and removing system components