Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems By Greg Henderson, Riyad Moe, Chris Kitten and Jose L.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL ERRORS AND TECHNICAL INACCURACIES. THE CONTENT IS PROVIDED AS IS, WITHOUT EXPRESS OR IMPLIED WARRANTIES OF ANY KIND. © 2010 Dell Inc. All rights reserved. Reproduction of this material in any manner whatsoever without the express written permission of Dell Inc. is strictly forbidden. For more information, contact Dell.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems Contents Introduction ........................................................................................................................................................... 2 Section 1: Cabling a Dell™ PowerEdge™ R310 or R410 With a Cable Management Arm (CMA) .......... 2 1.1 Connecting the CMA Cables to the System ....................................................................................... 2 1.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems Introduction This white paper covers recommended cable routing procedures for Dell™ PowerEdge™ R310 & R410 systems in the following racks: • • PowerEdge™ 4210/2410 PowerEdge™ 4820/4220/2420 If you are using the optional CMA, following these procedures will allow you to extend the system from the rack for service without powering down or disconnecting the cables.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems 1.2 Installing the Inner CMA Attachment Bracket As described in the Rack Installation Instructions, locate and attach the appropriate inner CMA attachment bracket based on which side you wish to mount the CMA. Use the bracket marked “A” for mounting the CMA on the left side, and the bracket marked “B” for mounting on the right side. See Figure 2. Figure 2: Attaching the Inner CMA Attachment Bracket 1.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems NOTE: For guidelines on how to route cables within the rack, refer to the Dell Best Practices Guide for Rack Enclosures white paper. 1.5 Left-Side Mounting Instructions 1. Install the CMA on the rear left side of the rails by attaching both CMA housings to the attachment brackets on the rails. 2. Route the cables through the CMA while avoiding twisting the cables. Use the hook and loop straps on the CMA to secure the cables. See Figure 4.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems Figure 5: Attaching the KVM Dongle to the CMA Basket KVM Dongle Use the hook and loop straps on the CMA basket to secure the KVM dongle. 4. Once you have routed all the cables through the CMA, dress the cable slack between the back of the system and the entrance of the CMA using the tie wraps (shown in yellow in all illustrations) provided in the CMA kit. 5. Clip off the excess length of material from the tie wraps.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems Figure 6: Left-Side Mounted CMA Installation 1.6 Right-Side Mounting Instructions Install the CMA on the rear right side of the rails by attaching both CMA housings to the attachment brackets on the rails. Follow steps 2-6 from the left-side mounting instructions in section 1.5. See Figure 7 for an example of a completed right-side mounted CMA installation.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems Section 2: Cabling a Dell™ PowerEdge™ R310 or R410 System Without a CMA NOTE: The CMA on Dell™ PowerEdge™ R310 & R410 systems is optional. Without the CMA installed, the system must be powered down and all cables disconnected before it can be removed from the rack. 2.1 Routing the Cables 1. Connect all applicable cables to the rear of the system and verify that all connections are secure. 2.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems Figure 9: Removing the CMA Brackets for Shallow Racks Section 3: Replacing a Power Supply on a PowerEdge™ R310 or R410 System With a CMA 1. 2. 3. 4. 5. 6. 7. Remove the tray from underneath the CMA as described in the CMA Installation Instructions provided with the CMA kit. Swing the CMA into the service position. Disconnect the power cord from the power supply and disengage the strain relief.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems Figure 10: Disconnecting the Inner CMA Attachment Bracket Figure 11: Replacing the Outer Power Supply Disconnected inner CMA bracket Section 4: Cabling a PowerEdge™ R310 or R410 System Installed in Static Rails NOTE: The CMA is compatible with the sliding rails only, not the static rails.
Cable Routing Procedures for Dell™ PowerEdge™ R310 & R410 Systems 3. Connect all applicable cables to the rear of the system and verify that all connections are secure. 4. Using the hook and loop straps, bundle the cables and secure them to either the left rail or right rail as described in the Rack Installation Instructions. See Figure 12 for an example of data cables that are secured to the left rail and power cables that are secured to the right rail (as viewed from the rear of the system).