Install Guide
Table Of Contents
- Dell EMC PowerSwitch S6100-ON Installation Guide March 2021
- About this guide
- S6100–ON system
- Site preparations
- NEBS compliance
- S6100–ON installation
- Power supplies
- Fans
- Management ports
- Dell support
- Specifications
- Chassis physical design
- IEEE standards
- Agency compliance
- USA Federal Communications Commission (FCC) statement
- European Union EMC Directive Conformance statement
- Japan: VCCI Compliance for Class A Equipment
- Korean Certification of Compliance
- Safety Standards and Compliance Agency Certifications
- Electromagnetic Compatibility (EMC)
- Product recycling and disposal
Figure 18. Chassis ground connector
a. Ground cable
b. Two-hole chassis ground connector
2. Install the grounding cables to the ground nuts.
The grounding cable must comply with your local electrical codes in size and color. Wires are typically green or green with a
yellow stripe.
NOTE:
For proper ventilation, position the chassis in an equipment rack or cabinet with a minimum of 5 inches (12.7
cm) of clearance around exhaust vents. The acceptable ambient temperature ranges are listed in the Environmental
Parameters section.
3. Tighten the M5 screws, torque between 18 and 24 in-lbs.
4. Connect the opposite end of the grounding cable to the nearest appropriate facility grounding post.
Figure 19. Cable connector
a. High-strand-count conductor
b. Two-holes for cable—.27 ±.02 DIA
24
S6100–ON installation










