Install Guide
Table Of Contents
- Dell EMC PowerSwitch S6100-ON Installation Guide March 2021
- About this guide
- S6100–ON system
- Site preparations
- NEBS compliance
- S6100–ON installation
- Power supplies
- Fans
- Management ports
- Dell support
- Specifications
- Chassis physical design
- IEEE standards
- Agency compliance
- USA Federal Communications Commission (FCC) statement
- European Union EMC Directive Conformance statement
- Japan: VCCI Compliance for Class A Equipment
- Korean Certification of Compliance
- Safety Standards and Compliance Agency Certifications
- Electromagnetic Compatibility (EMC)
- Product recycling and disposal
DC power supply connection
Each DC powered system comes with a set containing a prewired, 3-inch 8 AWG, power supply connector and a four-screw
wiring block. One set is provided for each DC PSU.
Figure 26. DC power connector and wiring block
1.
DC wire RTN 2. DC power connector
3. Two Captive screws 4. Release tab
5. PSU status LED 6. DC power socket
7. DC wire –48V
Figure 27. DC power connector ground
1.
Ground nut 2. Washer
3. Lock washer 4. Ground cable
5. Device grounding rod
1. Strip 1/2 inches of insulation from each of the power connector’s red and black wires, as shown.
2. Insert each of the power connector’s bare wire lengths into the wiring block. Insert red into one hole and black into the other
hole, as shown.
Power supplies
31