Install Guide
Table Of Contents
- Dell EMC PowerSwitch S6100-ON Installation Guide March 2021
 - About this guide
 - S6100–ON system
 - Site preparations
 - NEBS compliance
 - S6100–ON installation
 - Power supplies
 - Fans
 - Management ports
 - Dell support
 - Specifications
- Chassis physical design
 - IEEE standards
 - Agency compliance
 - USA Federal Communications Commission (FCC) statement
 - European Union EMC Directive Conformance statement
 - Japan: VCCI Compliance for Class A Equipment
 - Korean Certification of Compliance
 - Safety Standards and Compliance Agency Certifications
 - Electromagnetic Compatibility (EMC)
 - Product recycling and disposal
 
 
Fan module installation
The fan module in the S6100–ON is field replaceable.
Module slot 1 is on the left side of the chassis and module slot 4 is on the right side of the chassis.
CAUTION: DO NOT mix airflow directions. All fans must use the same airflow direction—reverse or normal. If
you mix the airflow direction, the switch detects the discrepancy, issues an alarm, and may auto-shutdown to
avoid heat damage to components. You must correct the mixed airflow direction.
1. Take the fan module out of the shipping box.
2. Use the grab handle and the orange tab to slide the module into the bay.
Figure 29. Fan module installation
a. Release tab
b. Fan module
Fan module replacement
NOTE: Never leave the fan partially inserted. The fan stalls if it is left partially inserted.
1. Use the grab handle and the orange tab to slide the fan module out of the bay.
2. Use the grab handle and the orange tab to slide the replacement module into the bay.
34
Fans