Setup Guide

-- Temperature Limits (deg C) --
----------------------- ---------------------------------------------
Minor Minor Off Major Major Off Shutdown
SwitchOn 47 46 50 49 NA
-- Temperature Limits (deg C) --
----------------------- ---------------------------------------------
Minor Minor Off Major Major Off Shutdown
FP-GE 47 46 50 49 NA
-- Temperature Limits (deg C) --
----------------------- ---------------------------------------------
Minor Minor Off Major Major Off Shutdown
FP-SFP+ 47 46 50 49 NA
-- Temperature Limits (deg C) --
----------------------- ---------------------------------------------
Minor Minor Off Major Major Off Shutdown
Bcm_Int 100 99 105 104 110
-- Temperature Limits (deg C) --
----------------------- ---------------------------------------------
Minor Minor Off Major Major Off Shutdown
Cpu_Int 95 94 NA NA NA
-- Temperature Limits (deg C) --
----------------------- ---------------------------------------------
Minor Minor Off Major Major Off Shutdown
Opt_Mod1 NA NA NA NA NA
-- Temperature Limits (deg C) --
----------------------- ---------------------------------------------
Minor Minor Off Major Major Off Shutdown
Opt_Mod2 NA NA NA NA NA
-- Temperature Limits (deg C) --
----------------------- ---------------------------------------------
Minor Minor Off Major Major Off Shutdown
Opt_Mod3 NA NA NA NA NA
-- Temperature Limits (deg C) --
----------------------- ---------------------------------------------
Minor Minor Off Major Major Off Shutdown
Opt_Mod4 NA NA NA NA NA
DellEMC#
Troubleshoot an Over-temperature Condition
To troubleshoot an over-temperature condition, use the following information.
1 Use the show environment commands to monitor the temperature levels.
2 Check air ow through the system. Ensure that the air ducts are clean and that all fans are working correctly.
3 After the software has determined that the temperature levels are within normal limits, you can re-power the card safely. To bring
back the line card online, use the power-on command in EXEC mode.
In addition, to control airow for adequate system cooling, Dell EMC Networking requires that you install blanks in all slots without a line
card.
NOTE
: Exercise care when removing a card; if it has exceeded the major or shutdown thresholds, the card could be hot to the
touch.
1196 Debugging and Diagnostics