Setup Guide

Securing the Chassis Ground
After you mount the chassis, secure the chassis ground as follows:
To properly ground the chassis, Dell Networking recommends using a 6 AWG
two-hole lug, #10 hole size, 63" spacing (not included in shipping). The two-
hole lug must be a UL recognized, crimp-type lug. To connect the ground
cable to the framework or cabinet and to mount the unit, use thread-forming
unit mounting screws that remove paint or nonconductive coatings.
CAUTION: Grounding conductors must be made of copper. Do not use
aluminum conductors.
NOTE: The rack installation “ears” are not suitable for grounding.
NOTE: Coat the two-hole lug with an anti-oxidant compound prior to
crimping. Also, bring any unplated mating surfaces to a shiny finish and
coat with an anti-oxidant prior to mating. Plated mating surfaces must
be clean and free from contamination.
NOTE: Never use the same bolts to secure multiple grounding cables.
1. Locate the two-hole chassis ground connector nuts on the chassis back.