Setup Guide

Figure 2. Chassis Ground Connector
2. Install the grounding cables to the ground nuts. The grounding cable
must comply with your local electrical codes in size and color (typically
the cable color is green or green with a yellow stripe).
NOTE: For proper ventilation, position the chassis in an equipment
rack (or cabinet) with a minimum of 5 inches (12.7 cm) of clearance
around exhaust vents. The acceptable ambient temperature ranges
are listed in the Environmental Parameters section.
3. Tighten the M5 screws (ensure torque is between 18 and 24 inch/lbs).
4. Connect the opposite end of the grounding cable to the nearest
appropriate facility grounding post.
Install the Hardware
9