Install Guide
Table Of Contents
- Dell EMC PowerSwitch Z9264F-ON Installation Guide August 2021
- Contents
- About this guide
- Z9264F-ON switch
- Site preparations
- NEBS compliance
- Z9264F-ON switch installation
- Power supplies
- Fans
- Management ports
- Before you install an OS
- Specifications
- Chassis physical design
- IEEE standards
- Agency compliance
- USA Federal Communications Commission FCC statement
- European Union EMC directive conformance statement
- Japan VCCI compliance for class A equipment
- Korean certification of compliance
- China warning
- Safety standards and compliance agency certifications
- Electromagnetic compatibility
- Product recycling and disposal
- Dell EMC support
Fan module replacement
To request a hardware replacement, see Dell EMC support.
CAUTION: Complete the following steps within one minute or the switch temperature could rise above safe
thresholds and the switch could shut down:
1. Slide the fan module out of the bay.
2. Slide the replacement module into the bay.
Fan air filter replacement
Environmental factors can decrease the amount of time required between air filter replacements. Check the environmental
factors regularly. An increase in temperature and/or particulate matter in the air might affect performance.
CAUTION: Check the fan air filters at six-month intervals and replace them as necessary. To accurately
determine air filter replacement intervals, regularly monitor the speeds of the cooling fans. An increase in
overall fan speed may indicate a clogged filter.
You must replace the fan air filters with new filters; you cannot clean and reuse the old fan air filters. Replacement filter media
must meet the requirements found in GR-63-CORE.
● Minimum dust arrestance of 65%, per ASHRAE Standard 52.1-1992. OR
● Minimum Efficiency Rating Value (MERV) of 2, per ANSI/ASHRAE Standard 52.2-2007.
CAUTION: For Network Equipment Building Systems (NEBS) compliance, use NEBS approved filters.
Use fan air filters with reverse blue-banded air flow switches—PSUs and fans. You can replace the air filters individually on each
fan within the switch without powering down a PSU module or disrupting traffic.
The fan air filter media slides into the frame from the top. No tools are required.
1. Determine which filters to replace.
2. Unlatch and remove the first module that needs the filter replaced.
3. Slide the existing filter upwards to remove it from the module.
4. Replace the filter with a new filter of the same size.
5. Reinsert the fan module.
6. Repeat for the remaining modules that need the filter replaced.
Fans