Dell EMC PowerSwitch Z9264F-ON Setup Guide March 2021 Rev.
Notes, cautions, and warnings NOTE: A NOTE indicates important information that helps you make better use of your product. CAUTION: A CAUTION indicates either potential damage to hardware or loss of data and tells you how to avoid the problem. WARNING: A WARNING indicates a potential for property damage, personal injury, or death. © 2017 - 2021 Dell Inc. or its subsidiaries. All rights reserved. Dell, EMC, and other trademarks are trademarks of Dell Inc. or its subsidiaries.
Contents Chapter 1: About this guide........................................................................................................... 4 Related documents............................................................................................................................................................. 4 Information Symbols...........................................................................................................................................................
1 About this guide This guide provides site preparation recommendations, step-by-step procedures for rack mounting and desk mounting, inserting modules, and connecting to a power source. CAUTION: To avoid electrostatic discharge (ESD) damage, wear grounding wrist straps when handling this equipment. NOTE: Only trained and qualified personnel can install this equipment. Read this guide before you install and power up this equipment. This equipment contains two power cords.
Information Symbols This book uses the following information symbols: NOTE: The Note icon signals important operational information. CAUTION: The Caution icon signals information about situations that could result in equipment damage or loss of data. NOTE: The Warning icon signals information about hardware handling that could result in injury. NOTE: The ESD Warning icon requires that you take electrostatic precautions when handling the device.
2 Site preparations The Z9264F-ON switch is suitable for installation as part of a common bond network (CBN). You can install the switch in: ● Network telecommunication facilities ● Data centers ● Other locations where the National Electric Code (NEC) applies For more information about the Z9264F-ON switch specifications, see Specifications. NOTE: Install the switch into a rack or cabinet before installing any optional components.
Rack mounting When you prepare your equipment rack, ensure that the rack is grounded. Ground the equipment rack to the same ground point the power service in your area uses. The ground path must be permanent. Switch ground Dell EMC recommends grounding your switch. Use the Z9264F-ON switch in a CBN. For more information, see Ground lug assembly. Fans and airflow Fan installation is done as part of the factory install based on stock keeping unit (SKU) type.
3 Z9264F-ON switch installation To install the Z9264F-ON switch, complete the installation procedures in the order presented in this section. Always handle the switch and its components with care. Avoid dropping the switch or any field replaceable units (FRUs). NOTE: ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap when handling the switch and its components.
screws ship attached to the switch. Before you install the DC switch in the dual-tray, attach the ground lug and bracket to the switch using the included screws and then attach the DC ground wire to the ground lug. The switch includes two installed M4 screws on the lower-left side of your switch. The DC switch also includes an assembled UL-certified GND lug with bracket, which is packaged separately. The AC switch does not include the UL-certified GND lug.
7. Attach the GND lug bracket assembly to your switch using the two removed screws, as shown. Torque the M4 screws to ±8–10 in-lbs. Figure 4. Ground lug assembly attached 8. Attach the other end of the ground wire to your rack ground point. 9. Install your switch into your rack using the Z9264F-ON installation instructions. Four-post rack assembly Due to the chassis weight, the Z9264F-ON switch does not support a two-post rack installation; you must install the switch in a four-post rack.
● Reliable earthing—Maintain reliable earthing of rack-mounted equipment. Pay particular attention to the supply connections other than the direct connections to the branch circuit, for example: use of power strips. ● Do not mount the equipment with the fan panel facing in the downward position. Switch installation and removal 1. Align the system with the rails and slide the system into the rack. 2. Tighten the screws on each side of the systems’s front panel, items 1 and 2. 3.
Optics removal Remove an optic by pushing the tab on the optic and sliding the optic from the port. When removing optics with direct attach cables (DACs) from the port, pull the release tab firmly and steadily. Before pulling the release tab, you may need to gently push the optic into the port to ensure that it is seated properly. Do not jerk or tug repeatedly on the tab. Switch startup Supply power to the Z9264F-ON switch after you mount it in a rack or cabinet. Reinspect your switch before power on.
4 Specifications This section lists the Z9264F-ON switch specifications. CAUTION: Operate the product at an ambient temperature not higher than 45°C (113°F). CAUTION: Lithium Battery Caution: There is a danger of explosion if the battery is incorrectly replaced. Replace only with same or equivalent type of battery. Dispose of the batteries according to the manufacturer's instructions. NOTE: For RoHS information, see Restricted Material Compliance.
Table 2. Environmental parameters Parameter Specifications Maximum non-operational altitude 39,370 feet (12,000 meters) Shock Dell EMC Spec SV0115 Table 3. AC power requirements Parameter Specifications Power supply 100–240 VAC 50/60 Hz Maximum current draw per system 4.7A/3.9A at 100/120V AC 2.35A/1.95A at 200/240V AC Maximum power consumption 1104.37W (based on 4.5W QSFP28) Typical power consumption 900W Table 4.
5 Support The support site provides documents and tools to help you effectively use your equipment and mitigate network outages. Through the support site you can obtain technical information, access software upgrades and patches, download available management software, and manage your open cases. The support site provides integrated, secure access to these services. To access the support site, go to www.dell.com/support/.