Owner`s manual

Back-Panel Connectors (Per RAID Controller
Module)
Two SAS OUT ports, it is recommended that you
use the first port for expansion to an additional
PowerVault MD3060e expansion enclosure. Only
one expansion port is supported at any given time.
NOTE: SAS connectors are SFF-8644
compliant.
Serial connector (debug port)
One 6-pin mini serial port
NOTE: For technical support use only.
Management Ethernet connector One 100/1000 Mbps Ethernet connection for out-
of-band management of the enclosure and the
second Ethernet port is reserved.
Power
AC power supply (per power supply)
Wattage 1755 W
Heat dissipation (maximum)
NOTE: Heat dissipation is calculated
using the power supply wattage rating.
The heat dissipation values are for the
entire system which includes chassis and
two controllers.
5988 BTU/hr
Voltage
NOTE: This system is also designed to be
connected to IT power systems with a
phase to phase voltage not exceeding
230 V.
220 V AC, autoranging, 50 Hz/60 Hz
Battery 6.6 V DC, 1100 mAh, 7.26 W Lithium ion battery
Environmental
NOTE: For additional information about environmental measurements for specific system
configurations, see dell.com/environmental_datasheets.
Temperature
Operating Continuous operation: 10 °C to 35 °C (50 °F to 95 °F) at
20% to 80% relative humidity (RH), with 26 °C
maximum dew point. De-rate maximum allowable dry
bulb temperature at 1 °C/300 m (1 °F per 550 ft) above
900 m (2952.75 ft).
47