Administrator Guide

Clear the Under Voltage Status for a Power Supply
Clear the under voltage status for an enclosure power supply to acknowledge that you are aware of it.
Steps
1. If the Storage Manager Client is connected to a Data Collector, select a Storage Center from the Storage view.
2. Click the Hardware tab.
3. In the Hardware tab navigation pane, expand Enclosures, then select and expand an enclosure.
The Enclosure view is displayed.
4. Under the selected enclosure, click Power Supplies.
The Power Supplies view is displayed.
5. In the right pane, select the power supply, then click Request DC Undervoltage Clear.
Clear the Swap Status for a Temperature Sensor
The swap status for a temperature sensor is set when the component that contains the sensor is replaced.
Steps
1. If the Storage Manager Client is connected to a Data Collector, select a Storage Center from the Storage view.
2. Click the Hardware tab.
3. In the Hardware tab navigation pane, expand Enclosures, then select and expand an enclosure.
The Enclosure view is displayed.
4. Under the selected enclosure, click Temperature Sensor.
The Temperature Sensor view is displayed.
5. In the right pane, select the temperature sensor, then click Request Swap Clear.
Clear the Minimum and Maximum Recorded Values for
Temperature Sensor
Clear the minimum and maximum recorded values for a temperature sensor to reset them.
Steps
1. If the Storage Manager Client is connected to a Data Collector, select a Storage Center from the Storage view.
2. Click the Hardware tab.
3. In the Hardware tab navigation pane, expand Enclosures, then select and expand an enclosure.
The Enclosure view is displayed.
4. Under the selected enclosure, click Temperature Sensor.
The Temperature Sensors view is displayed.
5. In the right pane, select the temperature sensor, then click Request Min/Max Temps Clear.
Replace a Failed Cooling Fan Sensor
This step-by-step wizard guides you through replacing a failed cooling fan sensor in the Storage Center without a controller outage.
Prerequisites
This wizard is only available for the SCv2000 series and SCv3000 series Storage Centers.
Steps
1. If the Storage Manager Client is connected to a Data Collector, select a Storage Center from the Storage view.
2. Click the Hardware tab.
3. In the Hardware tab navigation pane, expand either Controllers or Enclosures, then select and expand either a controller or an
enclosure.
Storage Center Maintenance