Owners Manual

Replacing a Power Supply/Cooling Fan Module
Use this procedure to replace a failed power supply/cooling fan module.
Prerequisites
Use SupportAssist to send diagnostic data to Dell Technical Support Services.
About this task
You can replace power supply/cooling fan modules one at a time without shutting down the storage
system
.
Steps
1. Press the power switch on the power supply/cooling fan module to turn it off.
2. Remove the hook-and-loop strap that secures the power cable and disconnect the power cable
from the power supply/cooling fan module.
3. Push the release tab on the power supply/cooling fan module and slide it out of the chassis using the
handle.
CAUTION: The power supply/cooling fan modules are heavy. To avoid injury, use both hands
while removing the module.
Figure 14. Removing a Power Supply/Cooling Fan Module
1. Power supply/cooling fan module 2. Storage system chassis
4. Slide the replacement power supply/cooling fan module into the chassis until it is fully seated and
the release tab clicks into place.
5. Connect and secure the power cable to the power supply/cooling fan module.
24
Replacing SCv2000/SCv2020 Storage System Components