Administrator Guide

Congure Storage Center to Use the Storage Center Update Utility
If the Storage Center is not connected to the internet, congure it to use the Storage Center Update Utility when checking for updates.
Before Storage Center can receive an update from the Storage Center Update Utility, a Storage Center distro must be loaded and the
Storage Center Update Utility service must be running.
Prerequisite
The Storage Center Update Utility must be setup and running.
Steps
1 If the Storage Manager Client is connected to a Data Collector, select a Storage Center from the Storage view.
2 In the Summary tab, click Edit Settings.
The Edit Storage Center Settings dialog box opens.
3 Click the SupportAssist tab.
4 Disable SupportAssist. Click Turn O SupportAssist.
5 Under Congure Update Utility, select the Enabled checkbox.
6 In the Update Utility Host or IP Address eld, type the IP address of the Storage Center Update Utility.
7 In the Update Utility Port eld, type the port of the Storage Center Update Utility.
8 Click OK.
Shutting Down and Restarting a Storage Center
Shutting down or restarting a Storage Center aects all controllers. Controllers can also be shut down or restarted individually.
NOTE
: For user interface reference information, click Help.
Shut Down All Controllers in Storage Center
Shutting down a Storage Center creates a system outage, during which time no I/O is processed. Use this process only as directed, for
example to replace hardware, to move the Storage Center to another location, or to shut down for data center power maintenance.
Prerequisites
An outage must be scheduled so that halting I/O does not impact your network.
I/O to the controllers must be halted.
Steps
1 If the Storage Manager Client is connected to a Data Collector, select a Storage Center from the Storage view.
2 In the right pane, click ActionsSystemShutdown/Restart.
The Shut Down/Restart dialog box opens.
3 From the rst drop-down menu, select Shut Down.
4 Click OK.
5 After the controllers have shut down, shut down the disk enclosures by physically turning o the power supplies.
Next step
After the outage is complete, see the Owner’s Manual for your controller for instructions on how to start the controllers in the proper order.
Related link
Set Storage Center Cache Options
Storage Center Maintenance
309