Table 19. Particulate contamination specifications (continued)
Particulate contamination Specifications
Conductive dust Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE: This condition applies to data center and non-data
center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
NOTE: This condition applies to data center and non-data
center environments.
Table 20. Gaseous contamination specifications
Gaseous contamination Specifications
Copper Coupon Corrosion rate <300 Å/month per Class G1 as defined by ANSI/
ISA71.04-2013
Silver Coupon Corrosion rate <200 Å/month as defined by ANSI/ISA71.04-2013
NOTE: Maximum corrosive contaminant levels measured at 50% relative humidity.
Thermal restriction matrix
Table 21. Thermal restriction matrix
Configuration
8 x 2.5-inch
NVMe
16 x 2.5-inch
SAS/ SATA + 8 x
2.5-inch NVMe
12 x 3.5-inch SAS/
SATA
Ambient
temperature
Rear storage No Rear Drives No Rear Drives No Rear Drives
CPU TDP/cTDP
105 W
5 x HPR fan
2U STD HSK
5 x HPR silver fan
2U STD HSK
5 x HPR silver fan
2U HPR HSK
35°C
120 W
5 x HPR fan
2U STD HSK
5 x HPR silver fan
2U STD HSK
5 x HPR silver fan
2U HPR HSK
35°C
135 W
5 x HPR fan
2U STD HSK
5 x HPR silver fan
2U STD HSK
5 x HPR silver fan
2U HPR HSK
35°C
150 W
5 x HPR fan
2U STD HSK
5 x HPR silver fan
2U STD HSK
5 x HPR silver fan
2U HPR HSK
35°C
165 W
5 x HPR fan
2U HPR HSK
5 x HPR silver fan
2U HPR HSK
5 x HPR silver fan
2U HPR HSK
35°C
185 W
5 x HPR fan
2U HPR HSK
5 x HPR silver fan
2U HPR HSK
5 x HPR silver fan
2U HPR HSK
35°C
205 W
5 x HPR fan
2U HPR HSK
5 x HPR silver fan
2U HPR HSK
5 x HPR silver fan
2U HPR HSK
35°C
220 W 5 x HPR fan 5 x HPR silver fan 5 x HPR silver fan 35°C
14 Technical specifications