Users Guide
62
|
MIB 对
表 11. IETF UPS MIB 对<(续)
变名称和相对 XML 对<=径 变单变类型OID
upsAlarmChargerFailed
UPS.BatterySystem.Charger.PresentStatus.InternalFailure
1.6.3.13 — —
upsAlarmUpsOutputOff
UPS.PowerSummary.PresentStatus.Good
1.6.3.14 — —
upsAlarmUpsSystemOff
相对 XML 对P径未实行
1.6.3.15 — —
upsAlarmFanFailure
UPS.PowerSummary.PresentStatus.FanFailure
1.6.3.16 — —
upsAlarmFuseFailure
UPS.BatterySystem.Battery.PresentStatus.FuseFault
UPS.PowerConverter.Input[1].PresentStatus.FuseFault
UPS.PowerConverter.Inverter.PresentStatus.FuseFault
1.6.3.17 — —
upsAlarmGeneralFault
UPS.PowerSummary.PresentStatus.InternalFailure
1.6.3.18 — —
upsAlarmDiagnosticTestFailed
相对 XML 对P径未实行
1.6.3.19 — —
upsAlarmCommunicationsLost
UPS.PowerSummary.PresentStatus.CommunicationLost
1.6.3.20 — —
upsAlarmAwaitingPower
相对 XML 对P径未实行
1.6.3.21 — —
upsAlarmShutdownPending
UPS.PowerSummary.DelayBeforeShutdown
1.6.3.22 — —
upsAlarmShutdownImminent
UPS.PowerSummary.PresentStatus.ShutdownImminent
1.6.3.23 — —
upsTestResultsSummary
UPS.BatterySystem.Battery.Test
1.7.3 整数 {1,2,3,4,5,6}
upsShutdownType
没有相对 XML 对P径
1.8.1 整数 秒
upsShutdownAfterDelay
UPS.PowerSummary.DelayBeforeShutdown
1.8.2 整数 秒
upsStartupAfterDelay
UPS.PowerSummary.DelayBeforeStartup
1.8.3 整数 秒
upsConfigInputVoltage
UPS.Flow[1].ConfigVoltage
1.9.1 整数 V