Manual
Table Of Contents

63
Specifications
|
Table 13. Electrical Output
208V Models 230V Models
Power Levels
(Rated at Nominal Inputs)
5600W 5600W
Regulation (Normal Mode) -6% to +6% of nominal voltage
NOTE: Varies based on auto-detected input voltage or customer settings.
Regulation (Battery Mode),
Nominal Voltage ±5%
-6% to +6% of nominal voltage
NOTE: Varies based on auto-detected input voltage or customer settings.
Voltage Waveform Sine wave
Output Receptacles (2) NEMA L6-30R, 30A
(4) IEC 320-C19, 20A
(4) IEC 320-C19; 16A for IEC,
20A for UL
(6) IEC 320-C13; 10A for IEC,
15A for UL
Table 14. Environmental and Safety
208V Models 230V Models
Operating Temperature Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Transit/Storage
Temperature
-15°C to 60°C (5°F to 140°F)
Relative Humidity 0–95% noncondensing
Operating Altitude Up to 3,048 meters (0–10,000 ft) above sea level
Audible Noise Less than 55 dBA on line/bypass mode (less than 75% load), room temperature
Fan Speed Low speed: when the load is <80%
High speed when the load is >80% or the UPS is in Battery mode
Surge Suppression ANSI/IEEE C62.41; 1991 Category B3
Safety Conformance UL 1778 4th Edition;
CSA C22.2, No. 107.3
UL 1778 4th Edition; CSA C22.2,
No. 107.3; IEC/EN 62040-1-1;
IEC/EN 60950-1
Safety Markings UL, cUL, VCCI UL, cUL, CE, GS, GOST, BSMI,
S-MARK, KC, NRCS, C-tick, CQC
EMC (Class A) FCC Part 15, ICES-003, VCCI IEC/EN 62040-2; EN 55022/CISPR 22;
ICES-003; CNS14757-2;
AS/NZS 62040.2;
FCC Part 15; KN22; GB7260.2;
EN 55024/CISPR 24