Support Matrix

Technical specifications
15 Dell EMC XC730 Series Hyper-Converged Appliance Support Matrix | A24
Type
Specification
Operating
Six consecutively run shock pulses in the
positive and negative x, y, and z axes of 40
G for up to 2.3 ms.
Maximum altitude
Operating
3,048 m (10,000 ft)
Storage
12,000 m (39,370 ft)
Operating altitude de-rating
Up to 35°C (95°F)
Maximum temperature is reduced by
1°C/300 m (1°F/547 ft) above 950 m (3,117
ft).
35°C to 40°C (95°F to 104°F)
Maximum temperature is reduced by
1°C/175 m (1°F/319 ft) above 950 m (3,117
ft).
Particulate contamination
NOTE: This section defines the limits to help avoid IT equipment damage and/or
failure from particulates and gaseous contamination. If it is determined that levels of
particulates or gaseous pollution are beyond the limits specified below and are the
reason for the damage and/or failures to your equipment, it may be necessary for you
to remediate the environmental conditions that are causing the damage and/or failures.
Remediation of environmental conditions is the responsibility of the customer.
Air filtration
Data center air filtration as defined by ISO
Class 8 per ISO 14644-1 with a 95% upper
confidence limit.
Note:
Applies to data center environments only.
Air filtration requirements do not apply to IT
equipment designed to be used outside a
data center, in environments such as an
office or factory floor.
Air entering the data center must have
MERV11 or MERV13 filtration.
Conductive dust
Air must be free of conductive dust, zinc
whiskers, or other conductive particles.
NOTE: Applies to data center and non-data
center environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a
deliquescent point less than 60% relative
humidity.