Submittal Sheet

MODEL ITG-CRD
(Up to 3 hour – Ceiling Radiation Damper)
Description
ITG-CRD Ceiling Radiation Damper is UL and cUL listed, and
exceeds UL 555C for use in 3-hour fire rated assemblies.
ITG-CRD is also Warnock-Hersey certified for use in fire
rated floor/ceiling or roof/ceiling assemblies.
Application
The ITG-CRD ceiling radiation damper employs a folded
curtain style blade for point-of-origin control of radiant heat
in a ventilation system
The ITG-CRD is to be installed horizontally in the ceiling
membrane for the floor/ceiling or roof/ceiling assemblies
with a re resistance rating up to and including 3 hours
Ventilation fans shall be ducted out of the plenum space
using any UL 181 Class 0 or Class 1 duct
UL listed as fan/damper assembly for the following Wood
Frame Construction designs: L521, L546, L558, L562, L574,
L576, L581, L583, L585, P522, P533, P538 and P545.
Intended for installation with the following UL Listed
Delta Electronic Fan Models ITG100, ITG80, ITG80H, ITG50,
ITG80LED, ITG70LED, and ITG50LED.
Features
Galvanized steel frame and sleeve
Folded ceramic curtain blade
165°F fusible link
Size: 8.0” x 8.5”
High temperature, non-asbestos, reinforced ber thermal
fabric
Warranty
3-year limited warranty
Folded ceramic curtain blade
Information is subject to change without notice or obligation
Ratings
UL 555C Fire Resistance Rating: 3 hour (horizontal, for
use in 1, 2, or 3 hour rated assemblies)
Listings
ACSFM listing: 3226-0368:104
UL 555C listing: R27832
Warnock Hersey listing #: 102881542SAT-001
Meets NFPA Standards: 90A and 101
Meets Building Code Standards: IBC, NBC, NFPA, SBC, and
UBC