Instruction Manual
      15    IOM-DPT-A: FEB 2014 
5.4.5. Insulation Resistance 
>100 MΩ @110V transmitters with gas arresters  
>100 MΩ @750V DC transmitters without gas arresters (Exi)  
5.4.6. High Voltage Test 
500V AC, or 750V DC, 1min, transmitters without gas arresters (Ex applications) 
75V AC, or 110V DC, 1min, transmitters with gas arresters 
5.4.7. Enclosure ingress protection 
EN 60529, IP 66,67 
5.5. Construction materials 
Electronics casing   High pressure cast of aluminium alloy, lacquered with chemical-resistant oxide 
enamel, colour yellow (RAL 1003), or stainless steel ss316L – not varnished. 
Shields - materials, diameters and lengths. 
Type of shield 
Shield 
Material of shield 
Connection type 
F [mm] 
L [mm] 
I [mm] 
SW1 
18h7 
100 
140, 200 
35 
65 
15HM, 
10H2M, 
316Lss 
- 
SW2 
24h7 
140, 200 
65 
15HM, 
10H2M, 
316Lss 
- 
GB1, GN1 
9 x 1 
100, 160, 
250, 400 
- 
316Lss 
M20x1,5, 
G1/2 
G1 
11 x 2 
100, 160, 
250, 400 
- 
316Lss 
M27x2, 
G1 
T1 
11 x 2 
100, 160, 
250, 400 
- 
316Lss 
Flange PN, DIN, ANSI 
6.  CONSTRUCTION. 
6.1. Measurement Principles. 
A signal from  measuring sensor, i.e. from  thermometer resistor Pt100  or  thermocouple,  corresponding  to 
measured medium temperature, is delivered to the input of analogue-digital converter and converted to digital 
form.  In  digital  form  it  is  sent,  through  an  optoelectronic  galvanic  barrier,  to  the  microcontroller.  The 
microcontroller reads measured values and, using built-in algorithms, calculates an exact value of temperature 
on the basis of these algorithms. Calculated value is shown on integrated LCD display, which can be configured 
depending on the needs (see p. 9.2.5). Digital value of measured temperature is converted to analogue signal 
4...20[mA]. Built-in modem BELL202 and implemented communication stack HART Rev.5.1 allow for the 
communication with the converter, using PC computer and appropriate software or communicator. 
The transmitter’s output is fitted with a radio-noise filter and other elements protecting against ESD. 
A block diagram of the transmitter is presented in Figure 1. 
DPT ... converters monitors the operation of their measuring systems and the correctness of calculations and in 
case when discrepancies occur they  inform about an error  displaying a  message on LCD display  and 
generating an alarm current in the current loop (depending on configuration). 
The measuring signal of sensor has a galvanic separation from measuring line. Thanks of that construction the 
measurement susceptibility at interferences is reduced as  well as the enlarged safety of work in the Ex and 
flameproof applications. 
6.2. Construction 
The basic  units  of  transmitter are: casing, shield  with process connection, measuring sensor  and  electronic 
units, transforming signal from measuring sensor into unified output signal. 