Instruction Manual
GENERAL 
The unit is manufactured, checked  and supplied in 
accordance with our published specification, and when 
installed  and  used  in  normal  or  prescribed 
applications,  with  the  lid  in  place  and  within  the 
parameters  set  for  mechanical  and  electrical 
performance, will not cause danger or hazard to life or 
limb. 
HEALTH AND SAFETY AT WORK ACT 1974 
WARNINGS 
1. THE  USERS  ATTENTION  IS  DRAWN  TO 
THE FACT THAT, WHEN THE UNIT IS ‘LIVE’ 
WITH  RESPECT  TO  ELECTRICAL  OR 
PRESSURE  SUPPLIES,  A  HAZARD  MAY 
EXIST  IF  THE  UNIT  IS  OPENED  OR 
DISMANTLED. 
2. UNITS  MUST  BE  SELECTED  AND 
INSTALLED  BY  SUITABLY  TRAINED  AND 
QUALIFIED PERSONNEL IN ACCORDANCE 
WITH APPROPRIATE CODES OF PRACTICE 
SO  THAT  THE  POSSIBILITY  OF  FAILURE 
RESULTING  IN  INJURY  OR  DAMAGE 
CAUSED  BY  MISUSE  OR  MISAPPLICATION 
IS AVOIDED. 
OPERATING PRINCIPLES 
A diaphragm is used to sense the difference between 
two pressures applied to either side of the diaphragm. 
The  diaphragm  transmits a  force proportional  to  the 
applied pressure difference to a push rod.  The rod is 
restrained by an adjustable spring.  When the force on 
the  rod  overcomes  the  spring  tension the  rod  moves 
and  operates  a  switch  or  switches.    On  reduction  of 
the applied pressure difference the force applied to the 
rod also falls, the rod is restored to its original position 
by the spring, and the switch or switches reset. 
TERMINAL ENCLOSURE CODE K (Fig 4 & 9) 
– INSTALLATION 
Terminal enclosure is rated IP65 for outdoor use. 
This is a certified  enclosure Zone 1 (Div 1) IEC 79-1 
BS  5501: Parts  1  and 5:  EN  50 014  and  EN  50  018 
EExd IIC T6. 
Instrument enclosure is certified to Zone 1 (Div 1) IEC 
79-1 BS 5501: Parts 1 and 5: EN 50 014 and EN 50 
018 Cenelec. 
WARNING:    Lid  and  adaptors.    It  is  a  safety 
requirement  that  at  least  5  full  threads  are  engaged 
when the unit is in operation.  Never operate the unit
unless  this  condition  is  met.    Do  not  use  greases  or 
lubricants  not  compatible  with  the  environment, 
process or aluminium. 
REPLACEMENT PARTS 
Use  only  factory  authorised  parts  and  procedures. 
The  only  parts  normally  recommended  for  site 
replacement are the microswitches. However, in some 
circumstances  other spares  kits  are available.    Apply 
for  details  quoting  the  serial  number  and  full  product 
code. 
WARRANTIES – SEE CONDITIONS OF SALE 
PRODUCT CODE 
ENCLOSURE 
MODEL 
ELECTRICAL ENTRY 
MATERIAL OF WETTED PARTS 
RANGE 
SWITCHING OPTIONS 
PROCESS CONNECTION 
OPTIONS AND TREATMENTS 
SPECIAL ENGINEERING   
ESGAAN DOWNWARD FACING CONNECTIONS 
INSTALLATION 
The instruments are  designed to be  mounted vertically. 
They can be mounted either direct to process or to a wall 
or  panel  using  the  backplate  provided.    Select  the 
mounting point so as to avoid excessive shock, vibration or 
temperature  fluctuation.    Instruments  should  be  mounted 
to avoid excessive heat transfer from the process lines or 
adjacent plant. 
If sudden changes of pressure (pulsations) are likely then 
we  recommend  that  snubbers  are  fitted  between  the 
process line and switch. 
Use  a spanner  to support  the  process connection  when 
fitting the instrument. DO NOT OVERTIGHTEN. 
WARNING: CHECK  THE CONNECTION  THREAD SIZE 
AND  SPECIFICATION  ON  THE  UNIT  TO  AVOID 
MISMATCHING  WITH  THE  PROCESS  CONNECTION 
ADAPTOR. SEE DIGIT 11 OF PRODUCT CODE. 
WIRING (Fig 1) 
Terminal Enclosure Version (Fig 4) 
Wire  in  accordance  with  local  and  national codes.   Use 
cables  no  larger  than  2.5  mm2  (14  AWG).    Deliver 
electrical connection through a suitable cable gland, which 
will  maintain  the  IP  rating  of  the  instrument.    Insert  bare 
wires fully into the terminal block and tighten securely. 
Keep wiring tails to a minimum. 
Flying Lead Version  
The leads  are factory  sealed so it is unnecessary to seal 
the  conduit  to  the  conduit  nipple.    However,  flying  leads 
must be terminated in accordance with local and national 
codes.  Each conductor is provided with an identity tag.  If 
these  become  detached refer  to the colour  code in the 
wiring diagram. 
CERTIFIED ENCLOSURES 
All  Series  GR  Pressure  Difference  Switches  can  be 
supplied  with  BASEEFA  certified  enclosures  to  the 
following standards: 
Zone 1 (Div 1) IEC 79-1 
BS 5501:  Parts 1  and 5: EN  50 014  and EN  50 018 
CENELEC.  Codes ‘H’ for aluminium and ‘R’ for stainless 
steel EExd IIC T6. 
All enclosures are suitable for outdoor use and the majority 
of products  are  rated IP66. Refer to  the product label 
and/or  leaflet.    Only  operation,  maintenance  or  repair 
procedures  either  contained  herein or  approved  by  Delta 
Controls  may  be  used,  to  avoid  rendering  the equipment 
unsafe in operation and / or nullifying the Certification. NO 
MODIFICATIONS ARE PERMITTED. 
Special Conditions for Safe Use 
The  integral  wires  shall  be  suitably  protected  against 
mechanical damage and be terminated within a terminal or 
junction facility suitable for the conditions of use. 
Electrical Adaptors 
Zone 1. Use only certified adaptors for Zone 1. 
EExe  for  increased  safety  installations  and  EExd  for 
Flameproof installations. 
References for Selection and Installation 
BSEN60079-14  Part4 for  all Enclosure  Codes  (Intrinsic 
Safety) 
BSEN 50014 Part 1 for Enclosure Codes H, R 
BSEN60529 IP RATING (Ingress Protection) 
MAINTENANCE 
Inspections should be carried out at quarterly to yearly 
intervals depending upon operating conditions. 
Where a terminal enclosure is fitted, isolate the unit  from 
process  and  power  and  remove  the  lid.    Check  all 
terminals for  tightness. Check that cable  tails are  not 
fouled or chafed.  Check for internal condensation. Rectify 
as necessary. 
It is recommended that instruments used to provide an 
alarm  are  operated  periodically  to  ensure  they  are 
functioning correctly. 
If  further  maintenance  is  required,  seek  advice  from 
DELTA  CONTROLS  before  attempting  repair  or 
replacement of parts. 
Note:  Should  the  diaphragm  fail  the  process  will  vent  to 
atmosphere  via  a control  orifice  without  pressurising  the 
switch  enclosure.  Periodically  ensure  the  vent area  does 
not become blocked and the vent plug has not degraded. 
Ensure that the vent area is not obstructed.  
CAUTION 
Moving parts  have  been treated  with a  water  repelling 
lubricant before leaving the factory.  Occasional inspection 
and  the  application  of  a  water  repelling  lubricant  is 
recommended  to  ensure  moving parts  remain free  under 
all conditions. 
WARNING: DOES NOT APPLY TO OXYGEN SERVICE. 
OPERATION 
Pressure  difference  switches  are  supplied  calibrated 
against  falling  pressure  difference  unless  otherwise 
specified.   Set Point Adjustment refers to falling pressure 
difference. Switching Differential is the difference between 
the  set  point  and  the  operating  value  on  rising  pressure 
difference. 
Set Point Adjustment: Models GR3/6 (fig 3) 
1 Isolate the instrument from the process. 
2 Adjustment may be carried out with the unit live. 
3 Loosen both cover screws. 
4 Rotate cover anti-clockwise to allow access. 
5 Using a screwdriver rotate the adjuster to obtain the 
 desired setting. Turn right to left to increase the setting. 
 An appropriate setting is shown by pointer against 
 reference scale. 
6 Rotate cover clockwise to close and tighten screws.
NOTE: For accurate setting, a suitable gauge must be 
used  in conjunction with  the above procedure.  Do not 
attempt to set the switch outside the scale limits.  Though 
the  unit  may  be  set  anywhere  within its  operation  range, 
for optimum performance, it is good practice to have a set 
point value between 25% and 75% of span. 
PROCESS CONFIGURATIONS (RANGE BC) 
For normal pressure difference operation, the connections 
are  made  to  the  High Pressure  (HP)  and  Low  Pressure 
(LP)  ports  as  appropriate.    For  single-ended  positive 
pressure operation, the HP only is used and the LP is left 
open to atmosphere.  The single-ended negative pressure 
operation, the LP only is used and the HP is left open to 
atmosphere. 
Use  a  breather  /  filter  in  the  vacant  port  of  single-ended 
operation. 
COMPOUND RANGE eg –12.5 to +12.5 mbar (RANGE BC) 
For normal operation, negative pressure may be applied to 
the  LP  port,  whereby  the  HP  port  is  left  open  to 
atmosphere and the set point is  between 0 and +12.5 
mbar. 
For reverse operation,  negative  pressure may be applied 
to  the  HP  port,  whereby  the  LP  port  is  left  open  to 
atmosphere and the set point is  between 0  and –12.5 
mbar. 
For positive pressures the opposite applies. 
It  is  recommended that  the  minimum  setting  is  to  be  not 
less than 5% of FS either side  approaching zero  (see  fig 
2). 
ISSUE E 02/10 
INSTALLATION, OPERATING AND 
MAINTENANCE INSTRUCTIONS FOR 
DIAPHRAGM ACTUATED SERIES GR 
PRESSURE DIFFERENCE SWITCHES 
(MODELS GR3 & GR6) 
SWITCH
0
NORMAL
REVERSE
PRESSURE
5 % FS
Fig 2
Fig 3
SCREW
DRIVER
LOCATION
SLOTS
LOWEST SET
POINT
HIGHEST
SET POINT
ADJUST
RIGHT TO
LEFT TO
INCREASE
SET POINT


