AC Drive User Manual

8
VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-9
Parameters Functions Settings
Factory
Setting
Customer
04-15 ACI1 Minimum frequency
(percentage of Pr.1-00)
0.0~100.0% 0.00
04-16 ACI1 Maximum frequency
(percentage of Pr.1-00)
0.0~100.0% 100.00
04-17 ACI2 Minimum current 0.0~20.0mA 4.0
04-18 ACI2 Maximum current 0.0~20.0mA 20.0
04-19 ACI2 Minimum frequency
(percentage of Pr.1-00)
0.00~100.00% 0.00
04-20 ACI2 Maximum frequency
(percentage of Pr.1-00)
0.00~100.00% 100.00
04-21 Analog Input Delay AVI 0.00~10.00 Sec 0.50
04-22 Analog Input Delay ACI1 0.00~10.00 Sec 0.50
04-23 Analog Input Delay ACI2 0.00~10.00 Sec 0.50
04-24 Summation of External
Frequency Sources
00: No functions
01: AVI+ACI1
02: ACI1+ACI2
03: ACI2+AVI
04: Communication master
frequency +AVI
05: Communication master
frequency +ACI1
06: Communication master
frequency +ACI2
00