AC Motor Drive User Manual

Chapter 4 Parameters|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11 4-55
40%
50%
60%
For 115V/230V Series
80%
90%
100%
2kHz
4kHz 8kHz
10kHz
12kHz
14kHz
15kHz6kHz
70%
Rated Current (%)
Carrier
Frequency
50 with mounting method A
40 with mounting method B
35 with mounting method A
25 with mounting method B
25 with mounting method A
15 with mounting method B
40%
50%
60%
For 460V Series
80%
90%
100%
70%
Carrier
Frequency
Rated Current (%)
2kHz
4kHz 8kHz
10kHz
12kHz
14kHz
15kHz
6kHz
50 with mounting method A
40 with mounting method B
25 with mounting method B
25 with mounting method A
15 with mounting method B
02.04 Motor Direction Control
Factory Setting: 0
Settings 0 Forward/Reverse operation enabled
1 Reverse operation disabled
2 Forward operation disabled
This parameter is used to disable one direction of rotation of the AC motor drive direction of
rotation.