Specifications

VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-12
Group 6 Protection Function Parameters
Parameters Functions Settings
Factory
Setting
Customer
06-00 Over-voltage Stall
Prevention
660.0V~820.0VDC
00: Disabled
780.0
06-01 Over-current Stall
Prevention during
Acceleration
20~250%
00: Disabled
150%
06-02 Over-current Stall
Prevention during
operation
20~250%
00: Disabled
150%
06-03 Over-torque Detection
Selection
00: Over-torque detection
disabled.
01: Over-torque detection
enabled during constant
speed operation (OL2),
and operation continues.
02: Over-torque detection
enabled during constant
speed operation (OL2),
and operation halted.
03: Over-torque detection
enabled during operation
(OL2), and operation
continues.
04: Over-torque detection
enabled during operation
(OL2), and operation
halted.
00
06-04 Over-torque Detection
Level
30~150% 110
06-05 Over-torque Detection
Time
0.1~60.0 Sec 0.1
06-06 Electronic Thermal Relay
Selection
00: Operate disabled.
01: Operate with a standard
motor.
02: Operate with a special
motor.
02
06-07 Electronic Thermal
Characteristic
30~600 Sec 60
06-08 Low Current Detection
Level
00~100% (00 disabled) 00
06-09 Low Current Detection
Time
0.1~ 3600.0 Sec 10.0
06-10 Low Current Detection
Treatment
00: Warn and Ramp to stop
01: Warn and Coast to stop
02: Warn and keep operating
01