Specifications

8
VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-15
Group 8 Special Parameters
Parameters Functions Settings
Factory
Setting
Customer
08-00 DC Braking Current Level 00~100% 00
08-01 DC Braking Time during
Start-up
0.0~60.0 Sec 0.0
08-02 DC Braking Time during
Stopping
0.00~60.00 Hz 0.0
08-03 Start-point for DC Braking 0.00~160.00 Hz 0.00
08-04 Momentary Power Loss
Operation Selection
00: Disable
01: Trace from top downward
02: Trace from bottom upward
00
08-05 Maximum Allowable Power
Loss Time
0.1~5.0 Sec 2.0
08-06 Speed Search Time 0.1~5.0 Sec 0.5
08-07 Maximum Speed Search
Current
30~150% 110
08-08 BB speed search method
00: Trace from top downward
01: Trace from bottom upward
00
08-09 Auto Restart Times after
Fault
00~10 00
08-10 Auto Restart Time after
Fault
00 to 60000 sec 600
08-11 Operation Frequency
Inhibition 1 UP
0.00~160.00 Hz 0.00
08-12 Operation Frequency
Inhibition
1 DOWN
0.00~160.00 Hz 0.00
08-13 Operation Frequency
Inhibition 2 UP
0.00~160.00 Hz 0.00
08-14 Operation Frequency
Inhibition
2 DOWN
0.00~160.00 Hz 0.00
08-15 Operation Frequency
Inhibition 3 UP
0.00~160.00 Hz 0.00
08-16 Operation Frequency
Inhibition
3 DOWN
0.00~160.00 Hz 0.00
08-17 Automatic Energy-saving 00: Energy-saving operation
disabled
01: Energy-saving operation
enabled
00
08-18 Automatic Voltage
Regulation (AVR)
00: AVR function enabled
01: AVR function disabled
02: AVR function disabled for
deceleration
00
a
08-19
Software Setting of the
Braking Level (the action
level of the braking resistor)
740V~820VDC
00:Disabled
760
a
08-20
Vibration Compensation
Factor
00~1000 00