Group 10 PID Controls
Parameters Functions Settings
Factory
Setting
Customer
10-00 Input Terminal for PID
Feedback
00: Disabled
01: Input via AI1
02: Input via AI2
03: Input via External
Reference
00
10-01 PID Control Detection Signal
Reference
1.0-6550.0 1000.0
10-02 PID Feedback Control
Method
00: Normal (Err=SP-FB)
01: Inverse (Err=FB-SP)
00
10-03 Proportional Gain (P) 0.0~10.0 1.0
10-04 Integral Time (I) 0.00~100.00 Sec 1.00
10-05 Differential Time (D) 0.00~1.00 Sec 0.00
10-06 Upper Bound for Integral
Control
00~200% 100
10-07 Primary Low Pass Filter Time 0.0~2.5 Sec 0.0
10-08 PID Feedback Signal Range 0.01 to 10-01 600.0
10-09 PID Feedback Signal Fault
Treatment Time
0. 0~3600.0 Sec
0.0: Disabled
0.0
a
10-10 PID Feedback Signal Fault
Treatment
00: Warn and RAMP stop
01: Warn and COAST stop
02: Warn and keep operating
01
10-11 V/F Curve Selection 00: Determined by group 01
01: 1.5 power curve
02: 1.7 power curve
03: 2 power curve
04: 3 power curve
00