00 - 02 AC Drive Status Indication 2 Factory setting: Read Only
Display
Bit 0~1: 00: Run LED is off and stop led is on. (AC Drive stopping)
01: Run LED is blink and stop led is on. (AC Drive deceleration to stop)
10: Run LED is on and stop led is blink. (AC Drive standby)
11: Run LED is on and stop led is off. (AC Drive running)
Bit 2: 1: Jog on.
Bit 3~4: 00: Rev LED is off and FWD led is on. (Forward)
01: Rev LED is blink and FWD led is on. (Reverse to Forward)
10: Rev LED is on and FWD led is blink. (Forward to Reverse)
11: Rev LED is on and FWD led is off. (Reverse)
Bit 5-7: Reserved
Bit 8: Master frequency source via communication interface
Bit 9: Master frequency source via analog
Bit10: Running command via communication interface
Bit11: Parameter locked
Bit12~15: Reserved
00 - 03
Frequency Setting (F) or Closed Loop Control Setting
Point
Factory setting: Read Only
This parameter displays the frequency command set by the user.
00 - 04 Output Frequency (H) Factory setting: Read Only
This parameter displays actual output frequency of the AC drive.
00 - 05
Output Current (A) Factory setting: Read Only
This parameter displays actual output current of the AC drive.
00 - 06 DC-BUS Voltage (U) Factory setting: Read Only
This parameter displays DC-BUS voltage of the AC drive.
00 - 07 Output Voltage (E) Factory setting: Read Only
This parameter displays output voltage of the AC drive.
00 - 08 Output Power Factor (n) Factory setting: Read Only
This parameter displays output power factor.
00 - 09 Output Power (kW) Factory setting: Read Only
This parameter displays output power of the AC drive.
00 - 10
Feedback Signal Actual Value Factory setting: Read Only
This parameter displays feedback signal value.
00 - 11 Feedback Signal (%) Factory setting: Read Only
This parameter displays feedback signal value(%).