Specifications
VFD-G Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-10
02 - 05 2-wire/3-wire Operation Control Modes Factory Setting: 00
Settings 00: 2-wire (#1), FWD / STOP, REV / STOP
01: 2-wire (#2), RUN/STOP, FWD/REV
02: 3-wire operation
This parameter sets the operation mode when operating by external terminals.
Please refer to 02-01.
02-05 External Terminal
00 (2-wire #1)
FWD / STOP
REV / STOP
REV:
DCM
W
D
F
REV/STOP
FWD/STOP
:("OPEN":STOP)
("CLOSE":FWD)
("OPEN":STOP)
("CLOSE":REV)
01 (2-wire #2)
REV / FWD
RUN / STOP
REV
DCM
W
D
F
FWD/REV
RUN/STOP
:("OPEN":STOP)
("CLOSE":RUN)
:("OPEN":FWD)
("CLOSE":REV)
02 3-wire
REV
DCM
WDF
VFD-G
FWD/REV
STOP
("OPEN":STOP)
("OPEN":FWD)
("CLOSE":REV)
RUN
EF
("CLOSE":RUN)
02 - 06 Line Start Lockout Factory Setting: 01
Settings 00: Disabled
01: Enabled
When enabled, the AC drive will not start when powered up with a run command applied.
The AC drive must see the run command transition from stop to run after power up. When
Line Start Lockout is disabled (also known as Auto-Start), the AC drive will start when
powered-up with run commands applied.
02 - 07 Reserved
02 - 08
Start-up Display Selection
a
Factory Setting: 00
Settings
Bit0~1: 00 = F LED
01 = H LED
10 = U LED (special display)
11 = Fwd / Rev
Bit2: 0 = Fwd LED / 1 = Rev LED
Bit3~5: 000 = 1st 7-step
001 = 2nd 7-step
010 = 3rd 7-step
011 = 4th 7-step
100 = 5th 7-step
Bit6~7: Reserved